DESCRIPTION:
he i3 family is founded on three principles: Installation Ease, Intelligence, and Instant Inspection.
The i3 line redefi nes installation ease with its plug-in design.This allows an installer to pre-wire the bases included withthe heads. The large wire entry port and in-line terminalsprovide ample room for neatly routing the wiring insidethe base. The base accommodates a variety of back boxmounting methods as well as direct mounting with drywallanchors. To complete the installation, i3 heads plug-in tothe base with a simple Stop-Drop ‘N Lock action.
i3 detectors offer a number of intelligent features tosimplify testing and maintenance. Drift compensationand smoothing algorithms are standard with the i3 line,to minimize nuisance alarms. When connected to the2W-MOD2 loop test/maintenance module, or a panelequipped with the i3 protocol, 2-wire i3 detectors arecapable of generating a remote maintenance signal whenthey are in need of cleaning. This signal is indicated viaan LED located at the module and the panel. To read thesensitivity of i3 detectors, the SENS-RDR is a wirelessdevice that displays the sensitivity in terms of percent perfoot obscuration.
The i3 series provides wide angle red and green LEDindicators for instant inspection of the detector condition,indicating: normal standby, out-of-sensitivity, alarm, orfreeze trouble conditions. When connected to the 2WMOD2loop test/maintenance module or a panel withthe i3 protocol, the EZ Walk loop test feature is availableon 2-wire i3 detectors. This feature verifi es the initiatingloop wiring by providing LED status indication at eachdetector.